Download:- From Card to Drive
- Switch Off power
- Take out interbus module and connect lenze card module
- Switch ON power
- It shows 0 at the start
- Select number for particular drive by pressing T3 button on the card module
- 1-Core Drive 1
- 2-Core Drive 2
- 3-Infeed Drive
6
Yellow and Green LED glows-it means parameter set
matches for that Drive
7
To start download program from card to drive-push T1
button and hold for 3 seconds
8
Display starts counting from 9 to 0
9
Push T1 again
10 LED
starts blinking- it means download starts
11 After
some time LED is idle-it means download finished
12 Switch
Off power and take out Lenze card module and connect interbus module
13 Switch
ON power
14 Check
for the loaded set of parameters on the HMI. It should be as follows:
Core 1 – 131
Core 2 – 131
In feed – 121
Arm – 311