CG Drive Trip Errors, Causes and Remedies

Sr. No.
Error
Means
Causes
1
UV
DC bus under voltage
Low AC supply voltage
Low DC bus voltage when supplied by an external DC power supply
2
OV
DC bus over voltage
Deceleration rate set too fast for the inertia of the machine
Mechanical load driving the motor
3
OI.AC**
Drive output instantaneous over current
Insufficient ramp times
Phase to phase or phase to ground short circuit on the drives output
Drive requires autotuning to the motor
Motor or motor connections changed, re-autotune drive to motor
4
OI.br**
Braking resistor instantaneous over current
Excessive braking current in braking resistor
Braking resistor value too small
5
O.SPd
Over speed

Excessive motor speed (typically caused by mechanical load driving the motor)
6
tunE
Auto tune stopped before
completion
Run command removed before autotune complete
7
It.br
I2t on braking resistor
Excessive braking resistor energy
8
It.AC
I2t on drive output current
Excessive mechanical load
High impedance phase to phase or phase to ground short  circuit at drive output
Drive requires re-autotuning to motor
9
O.ht1
IGBT over heat based on drives  thermal model
Overheat software thermal model
10
O.ht2
Over heat based on drives heatsink
Heatsink temperature exceeds allowable maximum
11
th
Motor thermistor trip
Excessive motor temperature
12
O.Ld1*
User +24V or digital output overload
Excessive load or short circuit on +24V output
13
O.ht3
Drive over-heat based on thermal model
Overheat software thermal model
14
O.ht4
Power module rectifier over  temperature
Power module rectifier temperature exceeds allowable maximum
15
cL1
Analog input 1 current mode, current loss
Input current less than 3mA when 4-20 or 20-4mA modes selected
16
SCL
Serial communications loss time-out
Loss of communication when drive is under remote control
17
EEF
Internal drive EEPROM trip
Possible loss of parameter values

18
PH
Input phase imbalance or input phase loss
One of the input phases has become disconnected from the drive (applies to 200/400V three phase drives only, not dual rated drives)
19
rS
Failure to measure motors stator resistance
Motor too small for drive
Motor cable disconnected during measurement
20
CL.bt
Trip initiated from the control word
Control word has initiated a trip
21
C.Err
SmartStick data error
Bad connection or memory corrupt within SmartStick
22
C.dAt
SmartStick data does not exist
New/empty SmartStick being read
23
C.Acc
SmartStick read/write fail
Bad connection or faulty SmartStick
24
C.rtg
SmartStick/drive rating change
Already programmed SmartStick read by a drive of a different rating
25
O.cL
Overload on current loop input
Input current exceeds 25mA
26
HFxx
trip
Hardware faults
Internal drive hardware fault (see the Advanced User Guide)

Sr. No.
Error
Means
Remedy
27
OVL.d
I x t overload (I = current, t = time)
Reduce motor current (Load)
28
hot
Heatsink/IGBT temperature high
Reduce ambient temperature or reduce motor current
29
br.rS
Braking resistor overload
See Menu 10 in the Advanced User Guide
30
AC.Lt
Drive is in current limit
See Menu 10 in the Advanced User Guide
31
FAIL
Failed attempt to read stick
An attempt has been made to read the stick when the drive was not disabled or tripped, or the stick is read-only

Baumuller Error No. 570

Power section auxiliary voltage supply . + safety relay

The error is triggered if both the auxiliary voltage supply (Error 566) or the power section (internal or external) and the safety relay (error 568) is not switched on. The voltage supply to the transistor triggering is released in the power section via the safety relay. The switching on sequence specified in the documentation must be complied with to avoid error messages when switching in a drive.
The error is fatal and leads to immediate shutoff of the drive controller. In this case the drive coasts to a standstill. Renewed release of the drive by the controller is prevented until the cause of the error has been corrected and the error has been acknowledged.

Source and Remedy 
Check the voltage supply of the auxiliary voltage, Safety relay is switched off
Incorrect activation of the safety relay Examine the activation of the safety relay. 

How to Make Programming of Lenze Drive 9300 Series

By Key Pad

  1. Press Program key
  2. Press Left Arrow(user mode) key
  3. Press Up Arrow (code list) key
  4. Press Right Arrow(enter) key
  5. Use Up and Down Arrow keys to see different parameters
  6. To change parameters first go to parameter no. C002
  7. Initially the C002 parameter is always 1. if we want to change the parameters, then first we have to make C002 as 0 otherwise it does not allow to change parameters.
  8. But be careful because once we make C002 as 0, all the parameters in the drive goes to factory set values. i.e. default values
  9. Then go to the parameters we want to change as per our requirement (press “Shift + Program” key for fast switching between parameters)
  10. Press Program key to set new value( set new values using Up and Down Arrow keys)
  11. To save the new value press “Shift + Program” key, then OK message appears on the display.
  12. Again press program key to return to last menu
  13. After changing all  parameters, go to C003 parameter
  14. Make C003 parameter as 1 to save and load all changes we made.

By Laptop

FROM LENZE DRIVE TO LAPTOP


1.  Connect LECOM to drive and RS232 cable to Laptop

2.  Connect 24 Vdc supply to connector no. 39(-) and 59(+)

3.  Open GDC ( Global Drive Controller) software from desktop

4.  It starts searching, 'IF not' Press F4 and then F2, select search

     Automatically reading parameter from drive

5.  Short commissioning 93XX window open

6.  Select code list

7.  Select Drive parameters and select write all parameters set to "File"

8.  Type file name e.g. 05ngr1.GDC and check the saving path.

9.  Press OK

10.Select F4 before quit the program GDC

11.Please check saved file in saving path positon.

FROM LAPTOP TO LENZE DRIVE

1.  Connect LECOM to drive and RS232 cable to Laptop

2.  Connect 24 Vdc supply to connector no. 39(-) and 59(+)

3.  Open GDC ( Global Drive Controller) software from desktop

4.  It starts searching, 'IF not' Press F4 and then F2, select search

     Automatically reading parameter from drive

5.  Short commissioning 93XX window open

6.  Select Drive parameters and select read all parameter set from file

7.  Read parameter set from file window open, select the file to be load, press      OK

8.  GDC warning window open, Press Yes, Code list display on window

9.  Select drive parameters and select write all parameter set to drive

10. Warning parameter set transfer window open, Press OK

11. Transfer variant selection-parameter set to drive window open
12. Press exchange unit

13. Parametersatztransfer window open

14. Start writing parameter to drive, after finish

15. Press F4

16. Close GDC

17. OFF/ON the power of drive