1 | Switch OFF the supply power. |
2 | Disconnect the module RTI 3 module. |
3 | Connect the ROD-3 module. |
4 | Connect the new DPO-1 card and check the jumper position must be on WRE. |
5 | Connect the cable to laptop and new DPO module. |
6 | Switch ON the supply power. |
7 | Open the Hyper terminal. |
8 | New connection window open. Type the name and select the COM1. |
9 | Setting of connection window open. |
10 | Follow procedure of A of page 2. |
11 | Press Reset button onthe new DPO-1 module. |
12 | Display B of page 3. |
13 | Give the speed 0 5 (5000) on the ROD-3 module by toggle switch. |
14 | Display C of page 3. |
15 | Type MONI for selection of program DPO-1, it is necessary. |
16 | Display D of page 3. |
17 | SIGNAL-NUMBER : 00 display, then type the 00. |
18 | SETTING OK? (Y/N) display, then type Y. |
19 | END display. |
20 | Press CTRL-E for display press speed. |
21 | Display E of page 4. |
22 | Press CTRL-R for reset counter. |
23 | Display F of page 4. |
24 | Press CTRL-D for clear reset-counter. |
25 | Disconnect into Hyper terminal. |
26 | Switch OFF the supply power. |
27 | Remove the ROD-3 module. |
28 | Connect the RTI 3 module. |
29 | Switch ON the supply power. |