| 1 | Switch OFF the supply power. |
| 2 | Disconnect the module RTI 3 module. |
| 3 | Connect the ROD-3 module. |
| 4 | Connect the new DPO-1 card and check the jumper position must be on WRE. |
| 5 | Connect the cable to laptop and new DPO module. |
| 6 | Switch ON the supply power. |
| 7 | Open the Hyper terminal. |
| 8 | New connection window open. Type the name and select the COM1. |
| 9 | Setting of connection window open. |
| 10 | Follow procedure of A of page 2. |
| 11 | Press Reset button onthe new DPO-1 module. |
| 12 | Display B of page 3. |
| 13 | Give the speed 0 5 (5000) on the ROD-3 module by toggle switch. |
| 14 | Display C of page 3. |
| 15 | Type MONI for selection of program DPO-1, it is necessary. |
| 16 | Display D of page 3. |
| 17 | SIGNAL-NUMBER : 00 display, then type the 00. |
| 18 | SETTING OK? (Y/N) display, then type Y. |
| 19 | END display. |
| 20 | Press CTRL-E for display press speed. |
| 21 | Display E of page 4. |
| 22 | Press CTRL-R for reset counter. |
| 23 | Display F of page 4. |
| 24 | Press CTRL-D for clear reset-counter. |
| 25 | Disconnect into Hyper terminal. |
| 26 | Switch OFF the supply power. |
| 27 | Remove the ROD-3 module. |
| 28 | Connect the RTI 3 module. |
| 29 | Switch ON the supply power. |