Baumuller Error No. 1000

USS - communication with axis not possible

The diagnostic system cyclically scanns the error storage of the individual drives. If the communication to one of the drives cannot be set up, this is signalled via the error number 1000.
No effect on machine control Only display at diagnostic system

Source and Remedy 
Error only at one controller:
Incorrect controller parameterisation Check controller parameter set:
USS Basic address (ID 329)
USS No. of Axles (ID 316) )

Error only at one controller:
Cable connection interrupted Check connection cable 
Connected connector on controller side (X23A and X23B) 
Connector connected on SDC side (X5) 
Connector connected to conversion module 

Error only at one controller: Wrong configuration in the diagnosis system Check configuration data (BAS) 
Error at several controllers: Cable connection interrupted Check the complete cable branch. The error lies between the last controller whose communications are running and the first controller with interrupted communication 
Error at several controllers: Wrong port address at diagnosis system Check configuration data (BAS)